For pricing and availability, please send an email to info@industrytechstore.com
SKU: FLS-IR3-AS21-H
Category: Flame Detectors
Brand:
Fire & Gas Detection Technologies Ltd
Part
Number: FLS-IR3-AS21-H
Entries:
2 x ¾” NPT
Material:
SS 316
Outputs:
4-20 mA Source or Sink HART
3 relays: Fire, Auxiliary &
Fault
RS-485 Modbus
Approvals:
ATEX, FM, IEC Ex, EN54-10, FM3260,
SIL2
IEC61508
Ultra-fast
detection mode – detection within 40
milliseconds
for fireballs or explosions
FlameSpec-IR3–HD is the
next generation of the IR3 flame detector. It is being introduced to further
enhance the protection and safety for these high risk and high value
industries.
The FlameSpec-IR3-HD
Triple IR (IR3) flame detector will detect fires and explosions extremely fast,
thus allowing preventative action to be initiated even more rapidly and
minimizing the consequences!
The unmatched detection
times and distances are:
40ms – for a fast fire burst or explosion
1.2s – for 1ft² (0.1m²) n-heptane pan fire
at up to 50 ft. (15m)
<4.1s – for 1ft² (0.1m²) n-heptane pan fire at
up to 230 ft. (70m)
Integral HD quality
video, with event recording, on top of the proven, superior capabilities of
Triple IR (IR3) flame detection, provides a very powerful safety tool to
protect personnel, plants, and processes.
The FlameSpec-IR3-HD
flame detector provides ultra-fast response, high performance, and reliable
detection of all types of hydrocarbon fires (visible and non-visible). The
detector addresses slow-growing fires as well as fast eruption of fire using
improved triple IR (IR3) technology. It operates in all weather and light
conditions with the highest immunity to false alarms.
In addition, the detector
provides high-definition (HD) video output of the monitored area with clear
imaging of a fire event and of personnel at distances up to 100 ft (30m). This
allows the rescue team to be aware of the exact situation before entering the
hazardous area. The detector automatically records video of any fire event (1
minute pre- and up to 3 minutes post alarm initiation). These features, along
with the built-in event logger, provide additional means to study the cause and
development of fire events for “lessons learned” reviews.