Shopping Cart

Schneider Acti9 iC60H 2P 16A C Miniature Circuit breaker- A9F54216

Brand:Schneider

For pricing and availability, please send an email to info@industrytechstore.com

Miniature Circuit breaker

Brand: SCHNEIDER

Part Number: A9F54216

 

This Acti9 iC60H is a multistandard low voltage miniature circuit breaker (MCB) with double tunnel terminals. It is a 2P circuit breaker with 2 protected poles, 16A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 30kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 10000A at 415VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuit against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 78.5mm. The weight is 0.25kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.

Range

Acti9

Product or component typee

Miniature circuit-breaker

Device short name

IC60N

Poles description

2P

Breaking capacity

15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2

10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1

42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2

30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2

15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2

10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

ambient air temperature for operation

-35…70 °C

Ambient air temperature for storage

-40…85 °C

Relative humidity

95 % at 55 °C